TM 9-6115-668-132.3.5 InstallationInstructions.2.3.5.1 ConnectBatteryCable.Below 32 °F (0 °C) the battery sets of two Generator Sets 150kW can be connected in parallel to increase capacity;below -22 °F (-30 °C) the battery sets must be connected in parallel. The battery cable is used to connect the two setsa. Connect battery cable as follows:‘(1)Remove protective cap (1, figure 2-11) from J3 SLAVE RECEPTACLE 24 VOLTS.(2) Connect battery cable (2) to the J3 SLAVE RECEPTACLE 24 VOLTS of each Generator Set 150 kW.Figure 2-11 Connect Battery Cable.2-46