TM 9-6115-668-13
Table 2-6 Oil change intervals.
125
250
500
(daily average)
Continuous operation at outside temperature
CD/SE 1)
0.5 . . . 1 %
<14 °F or >86 °F ( 10° C or >30° C)
0.5 . . . 1 %
>14 °F or <86 °F ( 10° C or <30° C)
<0.5 %
>14 °F or <86 °F ( 10° C or <30° C)
SHPD 2)
0.5 . . . 1 %
0.5 . . . 1 %
<0.5 %
<14 °F or >86 °F ( 10 C or >30° C)
>14 °F or <86 °F ( 10° C or <30° C)
>14 °F or <86 °F ( 10° C or <30° C)
If a higher grade oil is used after a long period of operation, perform the first change of the higher grade
oil at 20 operating hours. At the same time, change the oil filter as described in chapter 4.
2.3.4 Fuel SUpply.
2.3.4.1 Fuel Quality.
Do not use diesel fuel with a sulfur content greater than 1%. At temperatures below 32 °F (0° C) use only
winter diesel fuel with the appropriate additive or flow improver.
2.3.4.2 Refueling.
The Generator Set 150 kW tank has a capacity of 101.7 gallons (385 liters) of diesel fuel, including re-
serve. It can be filled with the fuel pump, a fueling nozzle, or a canister.
WARNING
The fuel in this Generator Set 150 kW is highly explosive. Do not
smoke or use open flame when performing maintenance. Fire and ex-
plosion could occur, resulting in severe personal injury or death.
CAUTION
The fuel pump must always be delivering diesel fuel during operation;
it will be damaged if it is allowed to run dry.
NOTE
If the LOW FUEL lamp (5, figure 2-10) lights up during operation, re-
2 - 4 3