TM 9-6115-660-13&PTable 5-5. Contactor OperationCONTACTORCONTINUITYNO CONTINUITYSTATUSBETWEEN PINSBETWEEN PINSPower NOT Applied32 and 3321 and 2211 and 12A1 and A2B1 and B2C1 and C2Power Applied21 and 2232 and 3311 and 12A1 and A2B1 and B2C1 and C23. If all multimeter indications are correct, install contactor terminal shield (3), four flat washers (2), andscrews (1).4. Replace contactor if any multimeter indication is not as listed in table 5-5,INSTALLATION1. Position contactor K1 or K2 (9) on studs (20).2. Install four flat washers (19), lock washers (18), and nuts (17).3. Refer to wiring diagram (figure FO-1) and tags installed in removal. Connect applicable terminal lugsof W9 wires to contactor terminals (16) X, Y, 11, 12, 21, 22, 32, and 33. Remove tags.4. If terminal shields (3) of contactor are installed, remove four screws (1), lock washers (2) and terminalshields (3).5. Remove nuts (4), lock washers (5), and flat washers (6) from contactor terminals (8) A1, B1, C1, A2,B2, and C2.NOTELeads W3, W4, and W5 (13, 14, and 15) must be installed along with leads W6, W7,and W8 when contactor K1 is being installed.6. Place free ends of jumpers W6, W7, and W8 (10, 11, and 12) on contactor K1 (15) terminals (16) A1,B1, and C1.7. Install flat washer (6), lock washer (5), and nut (4) on terminals (8) for A1, B1, and C1. Tightennuts (4).8. Place power cable leads (7) on contactor terminals (8) A2, B2, and C2. Remove tags.9. Install flat washers (6), lock washers (5), and nuts (4) on contactor terminals (8) A2, B2, and C2.10. Install terminal shields (3), two lock washers (2) and screws (1) on contactor (9).5-32