TM 9-6115-659-13&P
TEST
1. Repeat removal step above.
2. Refer to figure 5-17 and check continuity of relay coil between pins X1 and X2.
COIL DEENERGIZED
Figure 5-17. Relay K3-K6 Schematic.
Dangerous voltage exits on live circuits. Always observe precautions and
never work alone. Failure to observe this warning could result in severe
personal injury or death.
3. Attach 24 VDC power source across pins X1 and X2 of relay and check continuity of relay contacts
before and after relay is energized as listed in table 5-4.
Table 5-4. Relay Operation
4. If all multimeter indications are correct, perform installation procedures.
5. If any multimeter indication is not as listed in table 5-4 perform installation with new relay.
INSTALLATION
Install relay (3, figure 5-16) in relay socket (4) and secure with two washers (2) and screws (1).
5-30