TM 9-6115-658-13&P
3-5
Figure 3-1. GEN 1 or GEN 2 Indicator Lamp Fails To Light With
Corresponding Generator Set Running.
WARNING
SHUT DOWN GENERATOR SETS BEFORE
REMOVING INDICATOR LAMP. FAILURE TO
OBSERVE THIS WARNING COULD RESULT
IN SEVERE PERSONAL INJURY OR DEATH.
CHECK TO SEE IF CIRCUIT INTERRUPTER
LIGHT IS ON THE RESPECTIVE GEN SET
REPLACE LAMP
(PARAGRAPH 3-2.2)
OPEN
CLOSED
OK
NOT OK
REMOVE GEN 1 OR GEN 2
INDICATOR LAMP AND INSPECT
FOR SERVICEABILITY
PLACE CIRCUIT INTERRUPTER
SWITCH IN CLOSED POSITION
NOTIFY NEXT HIGHER
LEVEL OF MAINTENANCE