TM 9-6115-658-13&P
3-4
Section III. OPERATOR TROUBLESHOOTING
3-3 TROUBLESHOOTING.
3-3.1 Generator Set. Refer to TM 9-6115-639-13.
3-3.2 Trailer. Refer to TM 9-2330-202-14&P.
3-3.3 Power Plant. The following symptom index lists faults associated with switch box operation. Figures 3-1
and 3-2 provide a go/no-go flowchart of each malfunction. Each malfunction listed includes a reference to the
applicable figure that contains a chart that will help you determine probable causes and corrective actions to take.
The symptom index cannot list all faults that may occur, nor all tests or inspections and corrective actions. If a
malfunction is not listed or cannot be corrected by listed corrective actions, notify next higher level of maintenance.
SYMPTOM INDEX
Troubleshooting
Procedure
(Figure)
GEN 1 OR GEN 2 INDICATOR ON LAMP FAILS TO LIGHT WITH CORRESPONDING
GENERATOR SET RUNNING...................................................................................................................3-1
WITH GEN 1 OR GEN 2 ON LINE INDICATOR LAMP ON, NO POWER EXISTS AT
SWITCH BOX LOAD TERMINALS ............................................................................................................3-2