TM 9-6115-658-13&P
F-4
PARTS LIST
FIND
NO.
PART NO.
QUANTITY
DESCRIPTION
1
M22759/6-16-9
AR
WIRE, ELECTRICAL, 600 VOLT
2
M525036-106
31
TERMINAL, LUG, SMALL, RINGS,
TONGUE, FULLY INSULATED.
3
M23053/5-107-9
1
INSULATION SLEEVING, ELECTRICAL
(1.50 L)
4
M53367-4-9
AR
STRAP, TIEDOWN
5
M23053/5-105-9
70
INSULATION SLEEVING, ELECTRICAL;
(1.50 L)
NOTES:
1. BUNDLE WIRE HARNESS AT EACH BREAKOUT AND AT 3.00 MAX INTERVALS USING
TIEDOWN STRAP, FIND N0. 4.
2. HOT STAMP 97403-13229E5829. HOT-STAMPED MARKING SHALL PROVIDE
VISUAL CONTRAST AND SHALL BE IMPRESSED TO A DEPTH NOT EXCEEDING
ONE-FOURTH THE THICKNESS OF MATERIAL FOR PERMANENCY AND LEGIBILITY.
3. EACH WIRE SHALL BE IDENTIFIED BY HOT STAMPING ADDRESS DESIGNATIONS
USING .09-.16 HIGH BLACK CHARACTERS ON INSULATION SLEEVING, FIND NO. 3.
HOT-STAMPED MARKINGS SHALL PROVIDE VISUAL CONTRAST AND SHALL BE
IMPRESSED TO A DEPTH NOT EXCEEDING ONE-FOURTH THE THICKNESS OF
MATERIAL FOR PERMANENCY AND LEGIBILITY. ATTACH WITHIN TWO INCHES OF
BOTH END TERMINATIONS. ADDRESS SHALL CONSIST OF THE FROM
TERMINATION, A DOUBLE HEADED ARROW, AND THE TO TERMINATION.
EXAMPLE: XK3-2 AA TB1-1
4. STRIP AND TIN ENDS IN ACCORDANCE WITH MIL-STD-2000.
5. INSTALLED CRIMPED CONNECTIONS SHALL WITHSTAND AN AXIAL LOAD OF 8
POUNDS, SHALL HAVE CONTINUITY, AND SHALL SHOW NO EVIDENCE OF DAMAGE
OR ARCING WHEN CRIMPED WITH TERMINAL MANUFACTURERS RECOMMENDED
CRIMPING TOOL.
5. FOR SPARE PARTS PROCUREMENT ONLY:
A.
TEST REQUIREMENTS- WITH AN OHMMETER VERIFIES ELECTRICAL
CONTINUITY FOR EACH FROM-TO PATH SHOWN ON THE WIRE LIST.
B.
INSULATION RESISTANCE- MEASURE THE INSULATION RESISTANCE
BETWEEN ALL MUTUALLY INSULATED TERMINALS, INCLUDING THE SHELL OF
THE CONNECTOR, IN ACCORDANCE WITH ASTM D 257, EXCEPT THE DIRECT
VOLTAGE SHALL BE 1000 VOLTS + 10%. THE MINIMUM OBSERVED
RESISTANCE SHOULD BE 10 MEGOHMS.