TM 9-6115-604-34
NAVFAC P-8-633-34
Figure 2-12. Removal of Cabinet B Rear Cover
(9)
Working from the conduit box assembly (see Figure 2-14), pull the generator power and ground leads
through the conduit that connects cabinet B and the conduit box assembly. Coil the leads up and lay them
in the bottom of the conduit box assembly.
(10)
Disconnect the ac wiring harness (1, Figure 2-8) from the terminal board (2) and the two transformers (3)
located in the conduit box assembly. Coil up the wiring harness and lay it in the cable exit enclosure (4)
located underneath the conduit box assembly.
(11)
Remove battery charger in accordance with paragraph 4-20 of the Operator and Organizational
Maintenance Manual.
(12)
Remove the ac and dc lights and conduits above the generator in accordance with paragraph and 4-35 of
the Operator and Organizational Maintenance Manual.
(13)
Remove roof panels 5, 6, and 7 (see Figure 2-2) above the generator in accordance with paragraph 4-13 of
the Operator and Organizational Maintenance Manual.
(14)
Remove air cleaner assembly in accordance with paragraph 4-74 of the Operator and Organizational
Maintenance Manual.
2-39