TM 9-6115-604-34NAVFAC P-8-633-34(12)Verity the following:(a)The voltmeter reads 110 to 130 V ac.(b)The ammeter reads 3.68 to 3.74 amperes.(c)The microammeter reads 195 to 200 microamperes.(13)If the voltmeter and ammeter readings meet the conditions of steps (10) and (12), above, then powerfactor transducer PFT is good if micro ammeter readings also meet the stated conditions.NOTEIf the power factor transducer PFT tests out "good" in accordance with step (13), above, butnot in accordance with step (7), above, then there is something wrong with AC AMPERESmotor Ml 02 or circuit elements related to it.(14)If the voltmeter and ammeter readings do not meet the conditions of steps (10) and (12), above, then thetest of power factor transducer PFT is inconclusive, indicating only that some other element in circuit withthe transducer is defective.(15)If power factor transducer PFT is found to be defective, replace it in accordance with step h, below.h.Power Factor Transducer PFT Removal and Installation.WARNINGDo not work on energized equipment Generator set must be shut down. Transducer voltageand current Inputs and outputs are hazardous Performing maintenance on energizedtransducers may result In Injury or death.(1)Remove. See Figure 1 G8.(a) Tag and disconnect wires from power factor transducer PFT (8).(b) Remove screw and captive washer assemblies (7) to remove power factor transducer PFT (8).(2)Install. See Figure 10-8.(a) Install power factor transducer PFT (8) and secure with screw and captive washer assemblies (7).(b) Make wiring connections to power factor transducer PFT (8) as tagged. Remove and discard tags.i.Watt Transducer WMT On Equipment Test.WARNINGDo not work on energized equipment Generator set must be shut down Transducer voltageand current Inputs and outputs are hazardous. Performing maintenance on energizedtransducers may result In Injury or death.(1)With the generator set shut down, interconnect generator set output cable assemblies with a 750 kW, 0.8power factor load bank.(2)Start and operate the generator set in accordance with the Operator and Organizational MaintenanceManual.(3)Using a stopwatch, verify that KILOWATT HOURS counter CNTR registers 2.4 to 12.6 kilowatt-hours, in 60seconds, and also that AC KILOWATTS meter Ml 07 indicates 735 to 765 kilowatts. If so, then watttransducer WMT is good and test is over. Otherwise, proceed as follows.10-23
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business