TM 9-6115-604-34
NAVFAC P-8-633-34
1. REACTIVE CIRCUIT CABLE ASSEMBLY
7. GOVERNOR CIRCUIT CABLE ASSEMBLY
2. CLAMP
8. CLAMP
3. PLUG CONNECTOR
9. PLUG CONNECTOR
4. BUSHING
10. BUSHING
5. RLC MARKER BAND
11. GPC MARKER BAND
6. SHIELDED CABLE
12. SHIELDED CABLE
Figure 5-37. Parallel Cable Assemblies (Sheet 2 of 2)
Figure 5-38. Current Boost Module A101, Functional Diagram
5-51. MAINTENANCE OF CURRENT BOOST MODULE A101 (33, Figure 5-9).
a.
Inspect. See Figure 5-9. Check current boost module A101 for security of mounting, signs of burning and
security of electrical connections.
b.
Service. See Figure 5-9. Tighten any loose electrical connections and dean any dust or dirt that has
accumulated on the terminal block.
c.
Adjust. See Figure 5-39.
(1)
With the generator running at no-load, rotate the operation point adjustment control R13 fully
counterclockwise.
(2)
Reduce generator voltage to 240 volts.
(3)
Rotate the operation point adjustment control clockwise until the operation indicator (LED) turns off.
5-92