TM 9-6115-604-34NAVFAC P-8-633-341. REACTIVE CIRCUIT CABLE ASSEMBLY7. GOVERNOR CIRCUIT CABLE ASSEMBLY2. CLAMP8. CLAMP3. PLUG CONNECTOR9. PLUG CONNECTOR4. BUSHING10. BUSHING5. RLC MARKER BAND11. GPC MARKER BAND6. SHIELDED CABLE12. SHIELDED CABLEFigure 5-37. Parallel Cable Assemblies (Sheet 2 of 2)Figure 5-38. Current Boost Module A101, Functional Diagram5-51. MAINTENANCE OF CURRENT BOOST MODULE A101 (33, Figure 5-9).a.Inspect. See Figure 5-9. Check current boost module A101 for security of mounting, signs of burning andsecurity of electrical connections.b.Service. See Figure 5-9. Tighten any loose electrical connections and dean any dust or dirt that hasaccumulated on the terminal block.c.Adjust. See Figure 5-39.(1)With the generator running at no-load, rotate the operation point adjustment control R13 fullycounterclockwise.(2)Reduce generator voltage to 240 volts.(3)Rotate the operation point adjustment control clockwise until the operation indicator (LED) turns off.5-92