ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
Table 1-1. System Capacities and Detailed Data on Components (Continued)
2.
DC ELECTRIC AND CONTROL SYSTEM-Continued
Battery Charger BC1
Drawing Number:
80-7935
Input:
120 V ac, 50/60 Hz, single phase
Output:
24 V dc, 20 amperes (two ranges float
at 2.17 V dc per cell and equalize
Automatic AC Line Compensation:
at 2.33 V dc per cell
Mechanical Characteristics:
Automatic overload protection
(current limiting), fused ac input and dc
Operating Temperature:
output, automatic surge suppressors
-25 to +125 F (-31 to 51 °C)
Storage Temperature:
-65 to +155°F (-53 to 68°C)
Humidity Conditions:
To 100%
Manual Float/Equalizer Time:
0 to 24 hours
Manufacturer:
La Marche Manufacturing Company
Part Number:
A-46-20-24V-A1-040-080
FSCM:
92731
Coolant Temperature Switch WT2
Drawing Number:
80-7519
Rating:
10 amperes, 28 V dc
Connector:
MS3102R-14S-2P
Cover:
Aluminum, non-sealing
Cartridge:
Brass submersion type-1, vacuum filled
assembly and sealed
Circuit:
Two independent double break circuits,
normally open, to close on temperature rise.
Mechanical Life:
50, 000 cycles
Operation:
Circuit A and D (normally open)
contacts close at 217 2°F (102 ± 2C)
Circuit B and C (normally open)
contacts close at 208 2°F (97 2C).
Operating Temperature:
-25 to +125°F (-31 to 51C)
Storage Temperature:
-65 to +155°F (-53 to 68°C)
Humidity Conditions:
To 100%
Manufacturer:
The Nason Company
Part Number:
TC-152-208M/217M-4AN
FSCM:
85814
Coolant Level Switches S13 and S14
Drawing Number:
80-7650
Voltage Rating:
9 to 32 V dc
Current Rating:
1 ampere, maximum
Response Time:
1 second, typical
Probe Pressure Rating:
100 psi (690 kPa)
Mechanical Characteristics:
Negative ground, low alarm (actuates on
loss of liquid), fully encapsulated
Time Delay:
None
Humidity Conditions:
To 100%
Operating Temperature:
-40 to +250°F (-40 to 121C)
Storage Temperature:
-5 to +155 F (-54 to 68 C)
Manufacturer:
Robert Shaw Control Company
Part Number:
613-NLG
FSCM:
00543
1-19