ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12Table 1-1. System Capacities and Detailed Data on Components (Continued)1.HOUSING AND BASE ASSEMBLY-ContinuedFire ExtinguisherDrawing Number:80-7854Specifications:Carbon Dioxide Type, 15 pounds (7 kg),charged per MIL-E-24269ManufacturerThe Ansul CompanyPart Number:17224FSCM:03670Fan and Motor Assembly B103Drawing Number:80-7625Motor Rating:115 Vac, single phase, 50/60 Hz,1/10 horsepower, 1550 rpmFan Data : 10.00 diameter die formed steel oraluminum, dynamically balancedCapacity:Static Pressure of Water:(Cubic feet per minute):0 inch0.10 inch 0.125 inch0.250 inch830680610375Operating Temperature:-25 to +125 F (-31 to 51°C)Storage Temperature:-65 to +155°F (-53 to 68 C)Humidity Conditions:To 100%Manufacturer:Penn Ventilator CompanyPart Number:BG-18FFSCM:020132.DC ELECTRICAL AND CONTROL SYSTEMStorage Batteries BT1 through BT4Drawing Number:76-11252Specifications:12 volt, 200 amp hours, 20 hour rate.Conforms to Federal Specification W-B-131-8D, SAE 20T 8AManufacturer:General Battery CorporationPart Number:G268D1FSCM:08163Manufacturer:Prestolite Battery CorporationPart Number:8908XFSCM:48873Shielded CableDrawing Number:80-7963Material:Stranded tinned copper, vinyl insulation,clear nylon jacket, tinned copper braidshield, white vinyl jacket.Capacitance between conductors: 70 pF per footCapacitance between one conductor and otherconductor connected to shield:120 pF per footOperating Temperature:-25 to +125 F (-31 to 51 C)Storage Temperature:-65 to +155 F (-53 to 68 C)Humidity Conditions:To 100%Manufacturer:Belden Wire and Cable CompanyPart Number:9952FSCM:164281-18