ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
w.
FREQENCY Meter M103 (3. Figure 2-2).. Inspect for cleanliness and damage Check for secure attachment to
panel and for chipped, cracked, or loose cover glass and broken Indicators
x.
SYNCHRONIZING LIGHTS DS110 and DS111 (4. Figure 2-2). Inspect that lenses are secure and undamaged and
lamp sockets are secure In panel Check wiring security at rear of panel.
y
SYNCHROSCOPE Meter M106 (5. Figure 2-2). Inspect for cleanliness and signs of damage. Check for secure
attachment to panel and for chipped, cracked, or loose cover glass and broken Indicators.
z.
AC KILOWATTS Meter M107 (6. Figure 2-2). Inspect for cleanliness and damage. Check for secure attachment to
panel and for chipped, cracked, or loose cover glass and broken Indicators.
aa. AC KILOVARS Meter/Transformer M108 (7, Figure 2-2). Inspect for cleanliness and damage. Check for secure
attachment to panel and for chipped, cracked, or loose cover glass and broken indicators.
ab. FRFO ADJ Rheostat R102 (8. Figure 2-2). Inspect for cleanliness and damage to knob. Check security of knob on
shaft. Rotate full range In both directions while observing that travel Is smooth and uninterrupted and no evidence of
bent shaft Is noted Check rear of panel for security of mounting and wiring connections.
ac. POWFR FACTOR Meter M104 (9. Figure 2-2). Inspect for cleanliness and damage Check for secure attachment to
panel and for chipped, cracked, or loose cover glass and broken Indicators.
ad. GFN TEMP Meter M 105 (10. Figure 2-2). Inspect for cleanliness and damage Check for secure attachment to
panel and for chipped, cracked, or loose cover glass and broken Indicators.
ae. SYNCHROSCOPE Switch S115 (11. Figure 2-2). Inspect for cleanliness and signs of damage Check security of
panel mounting, wiring connections, and switch knob Check for satisfactory operation of click stops In both positions.
af. FRFOUENCY DROOP/ISOCHRONOUS Switch S117 (12. Figure 2-2). Inspect for cleanliness and signs of dam-
age Check security of mounting, wiring connections. Check that the switch turns freely In both positions and seats
properly In both positions.
ag. Phase Sequencing Indicator Lights DS112 and DS113 (14, Figure 2-2). inspect that lenses are secure and undam-
aged and lamp sockets are secure In panel Check wiring security at rear of panel.
ah. PHASE SEO. SEL, SW 119 (15, Figure 2-2). Inspect for cleanliness and signs of damage. Check security of panel
mounting, wiring connections, and switch handle Check for satisfactory operation of click stops In all three positions.
ai. PARALLEL /SINGLF Set Lights DS35 and DS36 (17, Figure 2-2). Inspect that lenses are secure and not cracked
and that lamp sockets are secure in panel. Check wiring security at rear of panel
aj. PARALLFL Switch S6 (18. Figure 2-2). Inspect for cleanliness and signs of damage Check security of panel
mounting, wiring connections, and switch handle Check for satisfactory operation of click stops in both PARALLEL
and SINGLE positions. Spring action should return switch handle to normal-vertical position.
ak. OPEN/CLOSFD Circuit Breaker Position Indicator Lights DS33 and DS34 (19, Figure 2-2). Inspect that lenses are
secure and undamaged and lamp sockets are secure In panel Check wiring security at rear of panel.
al. BREAKFR CONTROL Switch S4 (20. Figure 2-2). Inspect for cleanliness and signs of damage Check security In
panel mounting and wiring connections. Check handle operation in CLOSE position and In the TRIP position.
Spring-loaded handle must return to normal vertical attitude after each command operation with handle Index on the
target window. Target window should show red when last command operation was CLOSE and green when last
command operation was TRIP Check for proper PULL TO LOCK operation for handle In TRIP position. Handle
should remain locked until pushed for release and then must spring back to normal vertical position.
am. LOCAL RFMOTE Switch S2 (23. Figure 2-2). Inspect for cleanliness and signs of damage. Check security of panel
mounting, wiring connections, and switch handle Check for satisfactory operation of click stops in both local and
remote positions.
an. GFN/BUS VOLTMETER Switch S2 (24. Figure 2-2). Inspect for cleanliness and signs of obvious damage. Check
for security of panel mounting, wiring connections, and switch knob. Check for operation of click stops In all eight
positions.
3-71