TM5-6115-634-14&P
NAVFAC P-8-647-14&P
T0-35C2-3-445-14
TM-6115-14&P/1
6-4.
REPLACE FAULTY COMPONENT OF SPECIAL RELAY ASSEMBLY (cont)
c.
Replace faulty wiring harness:
(1) Remove all wires of faulty
wiring harness (6). (Not
shown).
(2) Attach new wiring harness
(6) using wiring diagram
figure 5-1.
d.
Replace faulty dc relay
assembly:
(1) Tag and remove wires from
faulty dc relay assembly
(7).
(2) Remove four screws (8) and
remove faulty dc relay
assembly (7).
(3) Install new dc relay assem-
bly (7) and secure with
four screws (8).
(4) Attach wires to new dc
relay assembly (7).
e.
Replace faulty instrument shunt:
(1) Tag and remove wires from
faulty instrument shunt
(9).
(2) Remove two screws (10) and
remove faulty instrument
shunt (9).
(3) Install new instrument
shunt (9) and secure with
two screws (10).
(4) Attach wires to new in-
strument shunt (9).
6-5