TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2brilliance. If light does not come on,adjust R3 on voltage regulator.Normally, R3 is set to provide R1 withan adjustment of ±10 percent of ratedrange.(7)When R3 and R1 are correctlyadjusted, a small change in R1 willturn the light bulb on and off. If lightstays either "full on", or does notcome on at all, the voltage regulatoris defective.NOTER4 on voltage regulator affects speedwith which light turns on and off.Normally it is factory set in theextreme clockwise position. Thissetting normally assures goodstability, but tends to slow theresponse time to the generator. Ifrotated counterclockwise, the systemresponse time becomes faster.However, if rotated too farcounterclockwise, the generatorvoltage may oscillate (hunt). It shouldthen be rotated clockwise well abovethe point where oscillating occurs.The system voltage stability is verycritical at no load.(8)Reconnect leads to T1 primary asthey were originally connected.(9)Reset potentiometer R4 to its originalposition.(10)Disconnect test setup and reinstallcover.WARNINGMAINTENANCE PERSONNEL SHOULDEXERCISE EXTREME CARE WHENTESTING EQUIPMENT WITH POWERON.b.On-EquipmentPowerOutputTest. Use amultimeter to check for the following outputsat the F+ and F- terminals at the loadsspecified below:No load- 12V DC at 1.1 amps250 KW load- 22 V DC at 1.9 amps500 KW load- 32V DC at 2.8 ampsc.Testing of Replaceable Components.Refer to figures 4-8 and 4-9 and check thefollowing components as indicated.(1)Check diodes CR8 (29), CR9 (26),CR13 (30), CR14 (25), CR15 (33),and CR16 (34) by disconnecting oneend of each diode and connecting anohmmeter (set at Rx100) across thediode. Note reading. Reverseohmmeter leads to the diode and notreading again. A good diode will readhigh resistance one way and lowresistance the other way. A shorteddiode will read full scale both waysand an open diode will read infinity(no reading) in either direction.Replace shorted or open diodes.Reconnect leads to good diodes.(2)Check sensing transformers T1 andT2 (24) by applying inputs of 120volts, 208 volts, 240 volts, 416 volts,80 volts, and 600 volts. Check with amultimeter for 31 volts across diodesCR5 and CR2. Check for 31 voltsacross diodes CR6 and CR3. Checkfor 31 volts across diodes CR4 andCR1. If these voltages are notpresent for all inputs, the sensingtransformers may be defective andmust be replaced.(3)After checking transformers T1 andT3, apply voltage to transformerinputs and verify opening and closingof relay K1 (23) contacts as indicatedin schematic (figure 4-9). Removevoltage and monitor contacts forclosing and opening as indicated.(4)Use an ohmmeter to check for 1.0ohms across resistor R25 (21) and150 ohms across resistor R1 (9).4-20. REPLACEMENT.a.RepairbyReplacementofComponents. Ifany of the diodes, transformers, relays, orresistors are defective, the voltage regulatoris repairable by replacing the defective4-15
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business