TM5-6115-593-34
NAVFAC P-8-631-34
T0-35C2-3-463-2
switch to the 60 Hz position.
h.
Loosen locknut and adjust R103 (54, figure
4-1) for 60 Hz operation. Monitor the
FREQUENCY meter on the Control Cubicle.
Tighten locknut (55).
i.
Proceed to normal operation of the set and
toggle the FREQUENCY SELECTOR switch
to the 50 or 60 Hz position depending on the
load requirement.
j.
Run
the
engine
until
the
coolant
temperature has stabilized and is normal.
k.
Turn the GAIN potentiometer clockwise until
the generator set becomes unstable. Then
back off this adjustment until generator set
just becomes stable.
l.
Rotate the STABILITY potentiometer 1/4
turn counterclockwise.
NOTE
The governor controller in the master
unit may have to be readjusted to
obtain a balanced load condition
between the master set and other units
in parallel operation. KW meters must
be
monitored
for
equal
readings
(proper load sharing).
4-14. REMOVAL AND REPLACEMENT. To gain
access to the governor controller, access panel must be
removed first, see paragraph 4-2.
WARNING
BEFORE
STARTING
ANY
MAINTENANCE
PROCEDURE,
SET
MAINTENANCE LOCKOUT SWITCH TO
LOCKOUT. DISCONNECT NEGATIVE
CABLE FROM BATTERIES. REMOVE
EXTERNAL
POWER
BY
OPENING
CB101
(EXTERNAL
POWER
BREAKER)
AND
DISCONNECTING
POWER CABLE FROM RECEPTACLE
J101 (120V RECEPTACLE).
a.
REMOVAL.
(1)
Disconnect
and
tag
all
wires
connected to the two terminal boards.
Remove warning plate to gain access
to terminals 1, 2 and 3 connections.
(2)
Referring to figure 4-1, remove the six
screws (52) and nuts (53) attaching
the
governor
controller
(56)
to
mounting bracket (62).
(3)
Remove potentiometer R103 (54)
from
mounting
bracket
(62)
by
removing shaftlock (55). Mounting
bracket (62) may be removed by
removing six screws (61).
b.
Replacement.
(1)
Attach
potentiometer
(54)
onto
mounting bracket (62) with shaftlock
(55).
(2)
Replace mounting bracket (62) with
six screws (61).
(3)
Attach governor controller (56) to
mounting bracket (62) with six screws
(52) and nuts (53).
(4)
Connect wires to terminal boards. Be
sure to connect potentiometer (54)
leads
to
terminals
16
and
20.
Remove tags from wires. Replace
warning plate.
(5)
Perform adjustment procedures in
accordance with paragraph 4-13.
4-15. TESTING. Bench testing is accomplished by
simulating various parameters connected to the unit.
The following items are required for the test setup: 20 to
40V DC source; 2 SPST switches; 35-ohm 10-watt
resistor; AC signal generator, capable of producing 60
Hz with 10 rms volts output; and a DC voltmeter to 25
volts.
NOTE
Before performing test, visually check
for damage to the chassis, terminal
block, or printed circuit board.
a.
Make the following connections to the
governor A106 terminal boards (see figure
4-5).
(1)
Connect 20 to 40V DC source to 12(+)
and 13(-)
.
4-10