TM 5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
Table 16-1. OPERATIONAL TESTS
MIL-STD-705B
TEST
PROCEDURE
TEST PARAMETER
1.
Start and Stop
503.1
Unit will start and stop
2.
Regulator and governor
608.1a
See tables 1-2 and 1-3
stability and transient
response (short term)
3.
Overspeed protection device
505.2a
2225 ±25 rpm
4.
Phase balance
508.1c
All L-L and L-N
voltages only.
5.
Circuit interrupter
512.1c
Instantaneously at 425
(short circuit)
±25 percent of rated
current
6.
Circuit interrupter
512.2c
8 ±2 minutes at 130
(overload trip)
percent of rated
current
7.
Circuit interrupter
512.3c
Instantaneously below
(undervoltage)
48 volts. 6 ±2 seconds
at 99 ±4 volts or less
8.
Circuit interrupter
512.3c
Not more than 1 second
(overvoltage)
after voltage has risen
to and remained at any
value greater than 163
±3 volts for not less
than 200 milliseconds
9.
High oil temperature
(4.7.2 of
255 ±3 Warning
MIL-G-52880)
265 ±3 Shutdown
10.
Low oil pressure protec-
515.la
Trip pressure 13 ±2 psi
tive device
Warning pressure 21 ±2
psi
11.
Reverse power protective
-
Refer to paragraph 16-8
device
12.
High coolant temperature
515.2a
Warning temperature +213
protective
±3F. (+100.5 ±1.70C)
Trip temperature +222
±3F. (+105.5 ±1.70C)
13.
Low fuel protective device
515.5
Refer to paragraph 16-9.
14.
Regulator range
511.lc
Test at both 50 Hz and
60 Hz. See tables 1-2
and 1-3
15.
Phase sequence (rotation)
507.1c
L1, L2, L3
16.
Frequency adjustment range
511.2b
See tables 1-2 and 1-3
17.
Parallel operation
Refer to paragraph 16-10
provisions
16-2