TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Table 16-1. OPERATIONAL TESTS - ContinuedMIL-STD-705BTESTPROCEDURETEST PARAMETER18.Malfunction indicator-Refer to paragraph 16-12system19.Maximum power640.1bIn excess of 110 percentof rated load20.Test parameters atAt 60 Hz500 KW at 1500 ft (457 m)at 90F (32.2C) 400 KWat 5000 ft (1524 m) at107F (41.7C)375 KW at 8000 ft (2435m) at 95F (25C)At 50 Hz417 KW at 1500 ft (457 m)at 90F (32.2C)332 KW at 5000 ft 1524 m)at 107F (41.7C)375 KW at 8000 ft (2435m) at 95°F (35C)CAUTIONPrior to performing any of the operating tests listed in table 16-1, ensure that the generator setis serviced with the correct fuel, oil, and coolant as listed on the data plate.16-3