TM 5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
Table 16-1. OPERATIONAL TESTS - Continued
MIL-STD-705B
TEST
PROCEDURE
TEST PARAMETER
18.
Malfunction indicator
-
Refer to paragraph 16-12
system
19.
Maximum power
640.1b
In excess of 110 percent
of rated load
20.
Test parameters at
At 60 Hz
500 KW at 1500 ft (457 m)
at 90F (32.2C) 400 KW
at 5000 ft (1524 m) at
107F (41.7C)
375 KW at 8000 ft (2435
m) at 95F (25C)
At 50 Hz
417 KW at 1500 ft (457 m)
at 90F (32.2C)
332 KW at 5000 ft 1524 m)
at 107F (41.7C)
375 KW at 8000 ft (2435
m) at 95°F (35C)
CAUTION
Prior to performing any of the operating tests listed in table 16-1, ensure that the generator set
is serviced with the correct fuel, oil, and coolant as listed on the data plate.
16-3