TM 5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2generator frequency (speed) and the voltage of each L-L and L-N condition. With the generator operatingat rated voltage, frequency, and no load, the maximum difference in the three line-to-neutral voltages shallbe not more than 1 percent of rated line-to-neutral voltage. The maximum difference between the voltagesof the 120-volt windings of any one phase shall be not more than one volt.d.Generatorwithseparateexcitation.(1)Determine from the data obtained in 16-13d(2) the maximum and minimum L-L and L-N voltages.(2)The voltage unbalance is the difference between the maximum and minimum L-L voltages. To expressthis in percent, divide this difference by rated L-L and multiply by 100.Voltage Unbalance (Coil) in percent = Vmax-Vmin X 100V Rated(3)Compare the results of step (2) above with the requirements.16-14. REGULATOR RANGE TEST.a.General.The voltage adjust device associated with the voltage regulator provided with the generator set musthave adjustment capable of varying the regulated voltage throughout the limits and under the various loadconditions and temperature ranges without causing the voltage droop of the set to exceed specification limits.The voltage adjust device also must be capable in some cases of providing and operating voltage other thanrated voltage for special types of equipment and to compensate the external line drop.b.Apparatus.Instrumentation for measuring load conditions, ambient temperature, and the generator field (orexciter field) voltage and current shall be as described in MIL-HDBK-705.c.PreparationforTest.(1)Preparation for test.(a)Connect the load and field instrumentation in accordance with the applicable figure of MIL-HDBK-705, Method 205.1, paragraph 205.1.10 for one voltage and frequency.(2)Test.(a)Start and operate the generator set and allow the set to stabilize at rated load, rated voltage andrated frequency. During this period record all instrument readings including thermal instrumention atminimum intervals of 10 minutes. If necessary, adjustments of the load, voltage and frequency maybe made to maintain rated load at rated voltage and frequency. Adjustments to the voltage andfrequency shall be limited to those adjustments available to the operator, specifically adjustments tothe voltage or frequency adjust advices. On sets utilizing a droop-type speed control system as theprime speed control, the speed and droop portions of the control may be adjusted. No otheradjustments to the voltage and frequency control systems shall be made. Adjustments to load,voltage or frequency controls shall be recorded on the data sheet at the time of adjustment.Stabilization shall be considered to have occurred when four consecutive voltage and currentreadings16-6
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business