TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Figure 15-5. Underfrequency Relay K116, Test Setupshould drop out at 46 ±0.1 Hz.b. Replacement. Remove relay (2, figure 15-3) bydisconnecting and tagging wires and removingfour screws (1). Remove relay (4) bydisconnecting and tagging wires. Remove fourscrews (1) and remove-relay from plateassembly (30).15-9. TRANSDUCERS. Remove transducers A103,A107, and A108 according to paragraph 15-9 b, and testas follows:a. Test.(1) Transducer A103. This transducer andgenerator set frequency meter are amatched set, and must be tested as aset. Refer to the Operator/Crew andOrganizational Level Maintenancemanual and remove frequency meterfrom the generator panel of the controlcubicle-WARNINGHIGH VOLTAGES PRESENT DURING TEST.(a) Connect a test setup as shown infigure 15-6.(b) Vary the frequency from lowestscale reading to full scale readingat 120 volts and at frequenciesbetween 48 and 53 Hz, thegenerator set meter shall readwithin 1 percent of the generatedfrequency (to the left); at 120 voltsand at frequencies15-6