TM5-6115-593-34NAVFAC P-8-631-34TO-35C2-3-463-2Figure 15-4. Undervoltage Relay K115, Test Setup(e) through (i) with the same results.(2) Underfrequency relay K116 (4, figure15-3).WARNINGHIGH VOLTAGES ARE PRESENT DURING TEST.(a) Connect relay to test setup asshown in figure 15-5.(b) Open switch S1 for 60 Hz test.(c) Adjust the frequency to 60 Hz andthe input voltage to 120 volts.Relay contacts should pick up.Lamp DS1 should light and DS2should extinguish.(d) Lower frequency slowly until relaycontacts drop out (lights transfer).Contacts should drop at 55 Hz±0.1 Hz.(e) Close switch S1 for 50 Hz test.(f) Adjust the frequency to 50 Hz andthe input voltage to 120 volts.Relay contacts should pick up.Lamp DS1 should light and DS2should extinguish.(g) Lower frequency slowly until relaycontacts drop out (lights transfer).Contacts15-5