TM5-6115-593-34
NAVFAC P-8-631-34
TO-35C2-3-463-2
NOTE
Low insulation resistance may be caused by
dirt or excessive moisture. Insulation failure
may be caused by wrong voltages, induced
voltages caused by opening field circuits too
quickly, oil and grease, high temperatures or
excessive vibration.
If the insulation fails to meet the test
standards, the generator may be dried
out by heat from a warm air oven, heat
lamps, or strip heaters. The temperature
should not exceed 167°F (75°C).
CAUTION
When oven drying, use a forced air circulation
oven, not a radiant type. Radiant type oven
would overheat some generator parts before
remote parts reached a satisfactory
temperature.
NOTE
If the generator must be dried out, then it is
necessary to revarnish the equipment
immediately after drying to prevent damage to
the unit.
(2)
Generator and excitation system test.
(a)
Generator Stator. Disconnect all
leads to voltage regulator and all
other points to completely isolate
the winding before meggering.
(b)
Generator Rotor. Disconnect field
leads from the rotating diode
assembly before meggering.
(c)
Exciter Stator. Disconnect both
field leads from terminals 1 and 2
of TB210.
(d)
Exciter Rotor. Check this only if
other windings have low insulation
resistance
as the leads must be unsoldered
from all diodes before meggering
(e)
Tag and disconnect the two leads
from the voltage regulator to
terminals in the lead separation
box. Connect positive side of a
DC ammeter to negative field
terminal (F-) and the positive
output of an adjustable DC source
to the positive field (F+) terminal.
Connect negative output of DC
source to negative side of DC
ammeter. The exciter field is rated
at 5.6 amps and 50V DC. The
adjustment should be set to
minimum voltage.
(f)
Select 60 Hz and start the engine.
With the speed at 1800 rpm, turn
on the adjustable DC power
supply. Adjust the DC voltage so
that the generator output voltage
(no load) reads 208 or 416 volts
depending on low or high voltage
connection. The exciter field
should draw approximately 1
ampere to produce rated voltage at
no load. The voltage across the
exciter field under these conditions
is approximately 10.8V DC, ±15
percent.
(g)
If the DC ammeter indicates
incorrect input exciter current to
obtain rated voltage in step (f)
above, the generator has failed. If,
however, the output is as specified,
the voltage regulator, control or
PM generator has failed.
(h)
Test rotating rectifier diodes
(paragraph 11-8b). If any
11-8