TM 5-6115-593-12TO 35C2-3-463-1STEP 1. PLACE ACPWRCKTBKR IN OPEN POSITION APPROXIMATELY 2 OR 3 SECONDS; THE ACPERCKTBKRCLOSEDLIGHT, SHOULD GO OUT.WARNINGSHUTTERS WILL SNAP SHUT RAPIDLY WITH CONSIDERABLE FORCE WHEN GENERATOR SETIS STOPPED. ENSURE ALL PERSONNEL ARE CLEAR OF SHUTTERS BEFORE PLACING MASTERSWITCHTO STOP. SERIOUS INJURY COULD RESULT.STEP 2. PLACE MASTERSWITCH IN STOP POSITION AFTER ALLOWING TO COOL BY OPERATING AT NOLOAD FOR APPROXIMATELY 5 MINUTES.STEP 3. AFTER ENGINE STOPS, REMOVE DC CONTROL POWER BY SETTING 24VDCCONTROLCIRCUITBREAKERTO OFFPOSITION.Figure 2-7. Stopping Instructions2-18