TM 5-6115-593-12TO 35C2-3-463-1STEP5.PRIOR TO CLOSING THE MAIN CIRCUIT BREAKER (AS EXPLAINED IN STEP 7, BELOW), CHECK GENFAULT INDICATORSAND ANNUCIATOR BY PLACING ANNUCIATORTEST SWITCH IN THE TEST POSITION. IF NONE OF THE LIGHTS ARE ONAFTER BEING TESTED PROCEED WITH STEP 6. IF A LIGHT DOES CONE ON. CORRECT THE INDICATED FAULT BEFOREPROCEEDING.STEP6.PLACE THE PARALLEL/SINGLEUNITOPERATIONSWITCH IN THE SINGLEUNITOPERATION POSITION.WARNINGPLACING ACPWRCKTBKR TO CLOSE APPLIES POWER TO OUTPUT LOAD TERMINALS AND LOADLINES. ENSURE ALL PERSONNEL ARE CLEAR OF OUTPUT LOAD TERMINALS. SERIOUS INJURY ORDEATH COULD RESULT FROM CONTACT WITH THE OUTPUT VOLTAGES.STEP7.PLACE THE ACPWRCKTBKR TO CLOSE POSITION FOR APPROXIMATELY 2 OR 3 SECONDS TO CLOSE THE MAIN CIRCUITBREAKER. CLOSED INDICATOR SHOULD COME ON.Figure 2-6. Starting Instructions (Sheet 2 of 3)2-16