TM 5-6115-593-12TO 35C2-3-463-1STEP1.CHECK LUBRICATING COOLANT LEVELS.STEP2.CHECK AIR BOX DAMPER POSITION AND RESET MANUALLY TO OPEN (SEE DETAIL A) IF REQUIRED.STEP3.CHECK BATTERY TERMINALS, MINUS (-) TO GROUND.STEP4.PLACE 24VDCCONTROLCIRCUITBREAKER TO ON POSITION ON GENERATOR PANEL.STEP5.ENSURE MAINTENANCE SWITCH IS IN OPERATION POSITION ON AC-DC CONTROL PANEL.STEP6.CHECK FUEL LEVEL BY PLACING BATTLESHORT SWITCH IN THE ON POSITION ON GENERATOR PANEL AND THEN THEMASTERSWITCHIN STARTPOSITION ON ENGINE PANEL.STEP7.RETURN MASTERSWITCH TO STOP AND THEN THE BATTLESHORT SWITCH TO OFF.STEP8.CHECK ENGFAULT INDICATORS AND ANNUCIATOR BY PLACING ANNUCIATORTEST SWITCH IN TEST POSITION ONGENERATOR PANEL. IF NONE OF THE LIGHTS ARE ON AFTER BEING TESTED, PROCEED WITH THE NEXT STEP. IF ALIGHT DOES NOT COME ON, CORRECT THE INDICATED FAULT BEFORE PROCEEDING.STEP9.CHECK VOLTAGE AND FREQUENCY REQUIREMENTS OF THE LOAD AGAINST THE VOLTAGE AND FREQUENCYCONNECTION OF THE SET.STEP10.PLACE AUTO/TRIP/MAN SWITCH IN MAN POSITION.Figure 2-5. Preparation for Starting (Sheet 1 of 3)2-12