4-42Change 10TM 5-6115-585-12NAVFAC P-8-623-12TO-35C2-3-455-1T M - 0 5 6 8 4 C / 0 5 6 8 5 B - 124-38. CONTROL CUBICLE ASSEMBLY.a. Test, On Equipment (see figure 4-33).NOTEWhen disconnecting leads from terminals, tapeleads to prevent electrical shorts.(1) Control Cubicle. Perform operational test oncontrol cubicle, checking for proper operation in each of theGenerator Set’s three modes using a voltmeter of knownaccuracy. Check that ac output voltage indicated on controlpanel matches output voltage at terminal board. Check thatGenerator Set does come to an EMERGENCY STOP whendc control circuit breaker (figure 2-3) is pulled. Test individ-ual components of the control cubicle as given below. Seefigure 4-33 for location of components.(2) With the generator operating at rated fre-quency, flash the generator field by placing the master switchon the control cubicle in the start position. If the generatorvoltage fails to build up after flashing, the control cubiclemay be defective.(3) Voltage Adjust Rheostat (R1). Turn theAmmeterVoltmeter transfer switch to its various positions.For each position of the switch, turn voltage adjust rheostatto its extreme positions. Voltage reading should be as fol-lows. Voltage adjust range shall be between 205 and 220Vfor the 120/208V, 3 phase, 4 wire connection. Between 114and 126V for the 120V, 1 phase, 2 wire connection. Between228 and 252V for the 120/240V, 1 phase, 3 wire connection.(4) Panel LightAssemblies (DS1) and(DS2). With a good incandescent lamp in place and 24 vdcpresent at terminals of panel light (panel light switch ON),check that lamps do light.NOTEBe certain panel light switch is OFF beforeinstalling or replacing panel light assembly.(5) Hour Meter (M2). Operate Generator Set.Check hour meter against a known accurate time source.Replace meter if necessary.(6) Battery Charging Indicator (M1). Connectmeter capable of reading at least 35 volts DC from terminalon battery charging indicator to ground. Operate GeneratorSet. With the needle in the yellow area, the meter should readbetween 18 and 27.5 volts. With the needle in the green area,the meter should read between 24.5 and 31.5 volts. NOTE:The apparent overlap in voltage between the yellow high andgreen low is the result of a plus or minus 1.5 volt metertolerance.(7) DC Control Circuit Breaker (CB2). OperateGenerator Set. Pull circuit breaker (CB2). If generator doesnot come to an emergency stop, stop the unit using masterswitch and replace breaker.CAUTIONDisconnect battery cable before making checks,unless otherwise noted.(8) Master Switch (S1). Disconnect battery. Tagand disconnect seven leads to master switch. Using an ohm-meter, check for continuity between terminals for each of thefive switch positions as given in table 4-3. If the continuity isnot found for each set of terminals listed, replace masterswitch.(9) Panel Light Switch (S2). Tag and disconnecttwo leads to panel light switch. Using an ohmmeter, test forcontinuity between terminals on switch. With the switch inthe OFF position, there should be no continuity. With theswitch in the ON position, there should be continuity.Replace switch if necessary.Table 4-3. Master Switch Continuity CheckSwitch PositionPREHEATOFFRUN AUX FUELRUNSTARTCheck for ContinuityBetween Terminals11-15NONE11-13-1711-1311-13-15 25-27-28
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business