TM 5-6115-584-34
NAVFAC P-8-622-34
TO-35C2-3-456-2
TM-0568C-34
(5) Mount coupling disc and fan assembly to the
rotor assembly (52) using screw (24) lock plate (25)
and retaining ring (26). Bend lock tabs flat against
head of screw (24).
(6) Mount exciter stator (17) to end bell (16)
using screws (14) and lockwashers (15).
(7) Place O ring (12) into end bell bearing
housing, attach terminal board (20) to the exciter
stator using screws (19) and nuts (18). Connect pre-
viously tagged and removed harness wire terminals.
(8) Mount end bell assembly (13) to the stator
assembly (53) using screw (10) and lockwashers (11).
(9) Install bearing retainer (33) and secure to end
bell (16) with lockwasher (9) and screw (6).
(10) Mount end bell cover (7) using screws (5)
and lockwashers (6).
(11) Mount screen (4) to generator, secure with
screw (l), nut (2) and lockwasher (3).
k. Test After Assembly. Rotate the generator
rotor shaft to be certain it rotates freely, that bear-
ings are smooth and rotor does not rub against stator.
l. Installation. Refer to paragraph 2-10 for mounting
of the generator.
m. Generator Winding Data.
(1) Generator frame assembly (see figure 8-3).
(2) Generator rotor (see figure 8-5).
(3) Exciter rotor assembly (see figure 8-4).
8 - 6