Table 17-3. Electric Winterization Kit Troubleshooting ChartMalfunctionWith S301 closed1. DS302 does notilluminate.2. DS301 does notilluminate.3. HTR1 and HTR2do not heat up.4. Coolant pump doesnot operate.5. Coolant pump failsto recirculateliquid.6. Coolant pump turnsover but fails todeliver fluid.7. Erratic or reducedoutput.8. Leakage.9. Motor failure.Probable causea.b.c.d.e.f.Defective wiring.Defective switch S301.Defective circuitbreaker CB301.Defective indicator.Defective diodes CR301to CR304.Defective transformer.Same as a. to f. above.a.b.c.a.b.Relay K301 does notenergize.Defective wiring.Heating element defec-tive.Same as a, b, c, e, andf in step 1 above.Defective pump.Faulty coolant pump. (Seemalfunction no. 4)Pump passages or bladeslots plugged withforeign matter.a.b.c.d.e.a.b.a.b.Air leak.Reduced voltage.Motor lag, low rpmScored cam ring bore.Foreign matter inpump blade slots.Face of seal cagescored, or damagedseal “O” ring.Seal face of adapterscored.Worn bearings.Burned armature.Corrective actiona.b.c.d.e.f.Repair or replace broken wiring.Check switch for continuity across contacts.Check circuit breaker for correct operationwith an ohmmeter.Check indicator for continuity; it shouldhave some resistance.Check diodes with ohmmeter.Refer to transformer test, paragraph 17-18.Same as a. to f. above.a. Test relay.Refer to paragraph 17-18.b. Repair or replace wiring.c. Replace.d. Same as a, b,b. Replace pump.Repair or replaceno. 4)c, e, and f in step 1 above.pump. (See malfunctionRemove pump from motor; disassemble andclean. Clean filter.a.b.c.d.e.a.b.a.b.Check tubing connections for leaks.Check voltage input to motor.Check motor brushes for excessive wear.Replace the cam ring.Remove pump from motor; disassemble andclean pump and filter.Disassemble and inspect seal cage face and“O” ring. Refinish or replace as required.Disassemble and inspect seal surface.Refinish or replace the adapter.Replace motor.Replace motor.17-9
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business