Table 17-4. Electric Winterization Coolant Pump Wear Limits
Figure 17-6. Wheel Mounting Kit
TM-5-6115-545-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
347
348
349
350
351
352
353
354
355
356
357
Table 17-5. Electric Winterization Heater Control Box Testing
Probable cause
Step
Test condition
Required result
for improper result
Check out procedure
1.
Position heater
Heater control box
Defective fuse F301.
Check
continuity
of fuse.
control box
indicators DS301
There should be con-
switch to ON
should illuminate.
tinuity.
and apply 230
Vat. Open
Defective switch 301.
Check
continuity
of switch
switch S2; see
when positioned to ON.
figure 17-5.
There should be con-
tinuity.
Defective circuit breaker CB301.
With
ohmmeter
, check
circuit breaker for
correct operation.
Defective indicator 301.
Check indicator for con-
tinuity.
There should
be some continuity.
Defective diodes CR301, CR302,
Check
diodes
with
CR303 or CR304.
ohmmeter
.
2.
Close switch S2.
Voltmeters
V2
Defective
transformer
T301.
See
transformer
test,
and V3 should
paragraph 17-18.
indicate 230
Vac and volt-
Defective
relay
K301.
Check
relay
per
meter V1
paragraph 17-18.
should indi-
cate approxi-
mately 30
Vdc, and DS302
should illumi-
nate.
17-14