PARALLEL WINDNG TEST.
CONNECT GOVENOR CONTROL
UNIT TO TEST EQUIPMENT AS
SHOWN
M2 SHALL READ 0-300 MA.
M3 SHALL READ 600-840 MA.
REVERSE POLARITY OF CONNECT-
IONS TO PINS J1-E AND J1-G.
M2 SHALL READ 600-840 MA.
M3 SHALL READ 0-300 MA.
TEST EQUIPMENT
REF DES
QUANTITY
DESCRIPTION
Re
1
RESISTOR, FIXED, 50,000 OHMS, 10 WATT
M2, M3
2
MILLIAMMETER, DC, 0-1000 MA
V1
1
DC POWER SOURCE
V2
1
DC POWER SOURCE
1
AC POWER SOURCE
ME 6115-545-34/7-10
Figure 7-10. Electric Governor Control Unit, Parallel Winding Test (400 Hz)
Figure 7-11.
Electric Governor Control Unit, Test Position for Unpotted Units
7-14