TM 9-6115866-13ItemNo.UNIT HOOD ASSEMBLY1.2.BeforeBeforePlatesFlaps3.BeforeGround straps4.BeforeCover for receptacles5.BeforeAir leading ducts (cooling airinlet for diesel engine)6.BeforeFuel CapTable 24 Operator Preventive Maintenance Checks and Services.NOTEIf the equipment must be kept in continuous operation, check and service only thoseitems that can be checked and serviced without disturbing operation. Make the com-plete checks and services when the equipment can be shut down.IntervalLocationItem to Check/ServiceProcedureThe fuel in this generator set150 kW is highly explosive. Donot smoke or use open flamewhen performing mainte-nance. Fire and explosioncould occur, resulting in 88vere personal Injury or death.Ensure key is in control cabinetpanel in the switch.Check that all plates are firmlyattached and readable.Check condition and operationof twist grips, gas cylinders, anddoor props.Inspect ground straps andground strap connections forlooseness, corrosion, or dam-age.Check condition and attach-ment of cover. Check for looseor missing hardware.Inspect air leading ducts forlooseness, damage, or dirt.Inspect fuel cap, chain, hard-ware, and strainer for loosenessor missing parts.Not Fully MissionCapable if:Flaps cannot be fullyopened or main-tained in the openposition.Ground straps areloose, damaged, orcorroded.Cover is damaged orloose.Air leading ducts areloose, damaged, ordirty.Fuel cap is missing.Change 12-21