TM 9-6115-668-13Table 2-2 Control Cabinet Assembly Description of Circuit Breakers.ItemNumber1.24 V DC/50 A circuit breaker, 1 - pole (F1)Circuit breakers K4 and K28; time relay K10; controlcabinet 24 V circuits (not including J2 and H7)2.24 V DC/6 A circuit breaker, 1 - pole (F2)Cabinet light H7, J2/24 V receptacle3.24 V DC/16 A circuit breaker, 1 - pole (F3)Speed governor assembly N1 , digital isochronusload sharing module N44.24 V DC/6 A circuit breaker, 1 - pole (F4)Auxilliary contactor K2 (charging control system, oilpressure, cylinder head and oil temperature)5.24 V DC/6 A circuit breaker, 1 - pole (F5)OIL PRESSURE, OIL TEMPERATURE, FUELLEVEL meters6.24 V DC/6 A circuit breaker, 1 - pole (F6)FREQUENCY meter, HOURMETER meter, bright-ness regulator N57.24 V DC/16 A circuit breaker, 1 - pole (F7)Auxilliary contactors K5, K7, K8, K9, K11 , K12, K19,K21, K23 and K27; time relays K3 and K13; thermis-tor relay F12, safety circuits8.24 V DC/16 A circuit breaker, 1 - pole (F8)Auxilliary contactor K24 (Tank maximum); FUELTANK PUMP ON illuminated pushbutton switch,FUEL TANK PUMP OFF pushbutton switch9.10.11.12.13.14.24 V DC/20 A circuit breaker, 1 - pole (F9)Auxilliary contactors K6, K14, K16, K18 and K20; timerelays K25 and K26; main contactor K1; voltage regu-lator N2; ssafety device N3120 V AC/6 A circuit breaker, 3 - pole (F10)FREQUENCY, KILOWATTS and VOLTAGE meters;voltage regulator N2; safety device N3120 V AC/16 A circuit breaker, 1 - pole(F11)Jl/l20 V 400 Hz double receptacle24 V DC120 A receptacle, 1 - pole (F101)Auxilliary contactors K101 to K105, K111, time relaysK106, K107 and K110, glowplug, air flap, fan motor,circuit breaker F10224 V DC/20 A circuit breaker, 2 - pole(F102)Oil pump, HEATING FAILURE lamp H10324 V DC/0,5 A circuit breaker, 2 - poleTime relay K108, auxilliary contact K109, solenoid(F103)valve, HEATING FAILURE lamp H103DescriptionProtects:2-9
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business