TM 9-6115-668-13
Table 2-1 Control Cabinet Assembly, Description of Controls and Indicators (continued).
Item
Number
15
AIR FILTER illuminated pushbutton switch,
red (H5, S17)
16
LOW FUEL lamp, amber (H15)
17
OIL TEMPERATURE meter, illuminated
P10)
l Green arc
l Red arc
Over temperature range
18
OIL PRESSURE meter, illuminated,
0 - 5 bar (P9)
19
20
21
22
READY TO START IF HEATING IS ON
lamp, green (H102)
HEATING FAILURE lamp, red (H103)
HEATING ON illuminated pushbutton
switch, green (S102, H101)
HEATING OFF pushbutton switch (S101)
23
FUEL LEVEL meter 0 - 1/1, illuminated
(P11)
24
HOURMETER meter (P8)
25
BATTLE SHORT switch (S21)
26
BATTLE SHORT lamp, amber (H17)
27
FREQUENCY ADJUST potentiometer,
10-gang (R4)
Description
Function
H5 lights up when the air filter is dirty; S17
cancels the fault message
Lights up when fuel level in fuel tank has dropped
to minimum tank level
Indicates engine oil temperature:
Operating temperature range
Indicates engine oil pressure
(>4 bar during operation)
Lights up when engine preheat time has elapsed
and engine can be started
Lights up in the event of a heating system failure
Turns heating system on:
H101 lights up when heating system is on
Shuts heating system off;
H101 goes out when heating system is off
Indicates level in fuel tank
Activated when diesel engine is operating
Shuts off safety and monitoring functions
Lights up when safety and monitoring functions
are off
Adjusts generator frequency:
l
Set between 4 and 5
For rated frequency indicated on FREQUENCY
meter (14)
2 - 4