paragraph 4.44
TM 9-6115-666-13
-
DANGEROUS
VOLTAGE
EXISTS ON LIVE CIRCUITS.
AL-
WAYS OBSERVE
SAFEI-Y
PRECAUTIONS
AND NEVER
WORK ALONE.
FAILURE TO OBSERVE
THIS WARNING
COULD RESULT IN SEVERE
PERSONAL
INJURY OR
DEATH.
NO
Measure
voltage at
YES
Kg/i 3 and KQ/A2:
24 VDC?
,
v
*
Repair or Replace
No
Measure
voltage
at K9/14 and
YES
cable 4 1
-
KQlA2 (Fl2/Tl
and /T2 open):
-
24 VDC?
v
Replace KQ
(PARAGRAPH
5.7)
v
NO
Measure
voltage at S6/i and
YES
-
KQ/A2 (Fl2/rl
and IT2 open):
-
24 /DC?
v
Repair or Replace
cable 52
v
NO
Measure
voltage
at S6/2 and
YES
KQ/A2 (Fi21Tl
and /T2 open):
Repare or Replace
Cable 56 from
S6l2 to Fl2/97
OK?
YES
Repair or Replace
cable 56
Continue on
page 4
I
Figure
5-l 7 GENERATOR
OVER TEMPERATURE
lamp lights
up during
operation
(sheet 3 of 4).
5 - 89