paragraph 5.10
page 2
paragraph 5.15
TM 9-6115-668-13
DANGEROUS
VOLTAGE
EXISTS ON LIVE CIRCUITS.
AL.
WAYS OBSERVE
SAFETY PRECAUTIONS
AND NEVER
WORK ALONE.
FAILURE TO OBSERVE
THIS WARNING
COULD RESULT IN SEVERE
PERSONAL
INJURY OR
DEATH.
YES
I Synchronous
generator
NO
YES
&
Check EPP Ill.
Refer to
TM 9-6115-669-13&P
1 YES
NO
Ft2: Disconnect
cables from
Ti and T2, and measure resis-
tance at cables 163 and 164:
>350 Q/68 F (20 C)?
Check Synchronous
generator.
Refer to
DMWR g-6115-668
I YES
NO
F12: Jumper between
Tl and T2.
Start Gen Set 150 kW.
Gen Set 150 kW shuts down?
NO
Figure
5-17 GENERATOR
OVER TEMPERATURE
lamp lights
up during
operation
(sheet 1 of 4).
5 - 87