paragraph 5.10page 2paragraph 5.15TM 9-6115-668-13 DANGEROUS VOLTAGE EXISTS ON LIVE CIRCUITS. AL. WAYS OBSERVE SAFETY PRECAUTIONS AND NEVER WORK ALONE. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH. YES I Synchronous generator NO YES & Check EPP Ill. Refer to TM 9-6115-669-13&P 1 YES NO Ft2: Disconnect cables from Ti and T2, and measure resis- tance at cables “163” and “164”: >350 Q/68 “F (20 ‘C)? Check Synchronous generator. Refer to DMWR g-6115-668 I YES NO F12: Jumper between Tl and T2. Start Gen Set 150 kW. Gen Set 150 kW shuts down? NO Figure 5-17 GENERATOROVER TEMPERATURE lamp lights up during operation (sheet 1 of 4). 5 - 87