TM 9-6115-666-13 DANGEROUS VOLTAGE EXISTS ON LIVE CIRCUITS. AL- WAYS OBSERVE SAFETY PRECAUTIONS AND NEVER WORK ALONE. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH. NO Measure voltage at YES - 57/t and K14lA2, V9: _ 24 VDC? v Repair or Replace cable ‘67” w NO Measure voltage at YES - S7i2 and Kt4jA2, V9: 24 VDC? 7 v NO Replace S7 Measure voltage at YES (PARAGRAPH 4.45) SSl3, Ki4lt and Kt4lA2, - V9: 24 VDC? v * * Repair or Replace NO Press S8 and measure YES cable “66” voltage at S8/4 and K14lA2, V9: 24 VDC? (PARAGRAPH 4.44) NO Measure voltage at YES - K16/22 and Ki4lA2, V9: _ 24 VDC? Repair or Replace cable “65” v Continue on page 3 Figure 5-9 AC CIRCUIT INTERRUPTER ON lamp does not light up (sheet 2 of 11). 5 - 53
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business