paragraph 5-7page 4paragraph 5.8TM 9-6115-668-l 3 - DANGEROUS VOLTAGE EXISTS ON LIVE CIRCUITS. AL- WAYS OBSERVE SAFETY PRECAUTIONS AND NEVER WORK ALONE. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH. NO r t=24s YES _ K3: green and amber _ LEDs light up? Check swrtching time (PARAGRAPH 5.8 Measure voltage at K3/10 and K6lA2: 24 VDC? YES Repair or Replace cables ‘40” and “0” NO Measure voltage at K3/15 and KBiA2: 24 VDC? YES v v I - NO Measure voltage at YES K5j72 and KS/A21 d 24 VDC? t v Repair or Replace cable “44” Figure 5-8 Generator voltage cannot be adjusted, or no voltage indication (sheet 3 of 7). 5 - 47
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business