TM9-6116-666-13 WAHNING DANGEROUS VOLTAGE EXISTS ON LIVE CIRCUITS. AL- WAYS OBSERVE SAFETY PRECAUTIONS AND NEVER WORK ALONE. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH. NO Measure voltage at YES - F7(lnput) and K3/A2: _ 24 VDC? t t Repair or Replace NO Measure voltage at YES cables ” 14” and “0” - F7(Output) and K3/A2: - 24 VDC? * t Replace F7 NO Measure voltage at YES (PARAGRAPH 4.63) IQ72 and K3lA2: 24 VDC? v t Repair or Replace NO Measure voltage at YES cable “4 I” m W71 and K3lA2: 24 VDC? Repair or Replace Continue on cable ‘39’ page 3 Figure 5-8 Generatorvoltage cannot be adjusted, or no voltage indication (sheet 2 of 7). 5-45