4-5.2.1 ASSEMBLY OF POWER PLANT.
Refer to figure 4-2A and assemble the AN/MJQ-40 as follows.
a. For unit A (set with switch box) connect power cable leads as follows.
(1)
Connect lead marked L1 to generator set load terminal L1.
(2)
Connect lead marked L2 to generator set load terminal L2.
(3)
Connect lead marked L3 to generator set load terminal L3.
(4)
Connect lead marked L4 to generator set load terminal L4.
(5)
Connect lead marked GND to generatot set GND terminal.
b. For units A & B remove 60 inch ground wire from accessory box and connect as follows.
(1)
Remove wing nut (1, figure 4-2A) two flat washers (2), hex nut (3), and flat washer (4)from ground stud
(5).
(2)
Place ground wire (6) over ground stud (5).
Ensure nut (3) is properly secured creating a good ground. Failure to observe this
warning could result in severe personal injury or death.
(3)
Install flat washer(4), hex nut (3), two flat washers (2), and wing nut (l).
(4)
Route ground wire (6) thru power cable sock (7).
(5)
Connect ground wire (6) to generator set ground terminal (8).
4-5.2.2
ASSEMBLY OF POWER UNIT.
Refer to figure 4-2A and assemble the PU-803 and PU-804 as follows.
a. Remove 60 inch ground wire from accessory box and connect as follows.
(1)
Remove wing nut (1, figure 4-2A), two flat washers (2), hex nut (3), and flat washer (4) from ground stud
(5).
(2)
Place ground wire (6) over ground stud (5).
Ensure nut (3) is properly secured creating a good ground. Failure to observe this
warning could result in severe personal injury or death.
(3)
Install flat washer (4), hex nut (3), two flat washer (2), and wing nut (l).
(4)
Route ground wire (6) thru power cable sock (7).
(5)
Connect ground wire (6) to generator set ground terminaI (8).
4-4.2