TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
CONTROLS, INSTRUMENTS, AND SWITCHGEAR (CONTINUED)
Frequency Range (Nominal):
Maximum Temperature
Effects on Accuracy:
Accuracy at 77F (25C)
(% RO at Nominal Frequency):
Output at Rated Input (DC):
Output Load Required:
Ripple (Peak):
Response Time:
Dielectric Test:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Manufacturer:
Part Number:
FSCM:
Synchronizer
Drawing Number:
DC Power Supply Voltage Input:
DC Power Supply Current Input:
AC Voltage Input (Main and General):
AC Current Input:
Alternator Frequency:
Breaker Closure Relay:
Breaker Closure Angle (Window):
Phase Error Adjustment Range:
Speed Capture Range:
Operating Temperature Range:
Weight:
Vibration:
Shock:
Dead Bus Voltage Sensing
Adjustment:
Voltage Matching:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Manufacturer:
Part Number:
FSCM:
50/60 Hz
0.5%
±0.25%
1 mA
O to 10 K ohms
Less than or equal to 0.25%
400 rms
1500 rms
-25° to +125F (-31° to 51C)
-65 to +155F (-53 to 68C)
To 100%
Scientific Columbus
4044, CT510A2
24561
80-7408
11 to 30 V dc
110 mA
50 to 50 V rms; 3 ranges
Less than 2 mA
30 to 100 Hz
Normally open (1250 V a); dual 5 amperes at 30 volts
±6 (continuously adjustable from ±30 to 0)
±10
±4 (based on 3250 Hz magnetic pickup signal)
-40° to 158° F (-40 to 70° C)
2.1 pounds (0.95 kg)
5 G at 5 Hz to 300 Hz
20 G's any plane
60 to 90% rating
Compatible with VMA671
-25 to +125F (-31 to 51C)
-65 to +155F (-53 to 68C)
To 100%
American Bosch Division
SY671 Y
01843
1-34