ARMY TM 9-6115-60412NAVY NAVFAC P-8-633-12(2) Replace See figure 5-2.(a) Tag and disconnect wiring from MASTER switch S9R (24) terminals.(b) Remove locking nut and lockwasher from RCM front panel and remove MASTER SWITCH S9Rfrom the rear panel.(c) Install jumper wire across terminals 2 and 6 of replacement MASTER switch S9R.(d) Install MASTER switch S9R (24) from rear of RCM panel.(e) Secure switch at front RCM panel with lockwasher and locking nut.(f) Connect wires as tagged Remove and discard tags.(g) Close RCM panel and secure by locking three oval studs across the top of the panel.r. HIGHCOOLANTTEMP/LOWOILPRESSURE/FAULTLights(25,Figure5-2). These lights Illuminate toindicate that a fault condition has occurred at the main generator set.Do not touch exposed electrical connection when a source of power such asutility power or another generator set is connected to the load terminals. Death orinjurymay result from failure to observe this warning.(1) Test Prior to performing individual tests on fault lamps and lamp holders, press the ANNUNCIATOR TESTswitch S1 5R with the RCM energized, to verify both the availability of 24 V dc control power and theexistence of an RCM fault indicator malfunction Horn LS1 R should sound and the HIGH COOLANTTEMP, LOW OIL PRESSURE, and FAULT indicators (DS3R, DS2R, DS103R, respectively) shouldlight Perform the following tests on any fault lamp that falls to light when the ANNUNCIATOR test switchS15R is pressed.(a) Open the RCM panel by unlocking three oval studs across the top of the panel.(b) Set multimeter to 50 V dc scale and check for 24 V dc at lamp holder (27) terminals ofmalfunctioning indicator (25) at the same time that ANNUNCIATOR TEST switch S15R is beingpressed Press the ALARM SILENCE switch S16R to prevent horn LS1R from sounding when test isbeing performed.(c) If 24 V dc is not present at lamp holder (27) terminals, check blocking diodes D1 R through D6R(depending on malfunctioning indicator) mounted on terminal block TB1R (11, Figure 5-1) InsideRCM chassis. Test diodes as follows:1Release ANNUNCIATOR TEST switch S15R and test diode with multimeter set to RX1 scale.Connect multimeter leads to diode terminals and then reverse multimeter connections to diodeunder test.2Diode resistance reading should be infinite ohms going one way and zero ohms when multimeterleads are reversed. Replace any diode that fails to meet this test. Tag and disconnect wiring todiode by polarity for correct Installation of replacement component. If diodes are good, tracewiring back to main generator set using FO-1. Trace back through main generator set circuitsuntil defective components are found Repair or replace as necessary.(d) If 24 V dc is present at lamp holder (27) terminals, replace lamp (25) with a known good lamp. Ifknown good replacement lamp still does not light, replace the lamp holder (25).(2) Replace.(a) Remove lens (26) covering lamp (25).(b) Tag and disconnect wiring from lamp holder (27).(c) Remove lamp holder (27) from panel by removing attaching hardware from rear.5-25
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business