ARMY TM 9-6115-60412p. PARALLELIndicatorDS35RandSINGLESETIndicatorDS36R(21,Figure5-2).These lights provide visualindications of the PARALLEL switch positions.Do not touch exposed electrical connection when a source of power such asutility power or another generator set is connected to the load terminals. Death orinjury may result from failure to observe this warning.(1) Test See Figure 5-2. When a lamp fails to light when expected proceed as follows.(a) Open the RCM panel by unlocking three oval studs across the top of the panel.(b) Set multimeter to 120 V ac scale and check for presence of 120 V ac at lamp holder (23) terminals.If 120 V ac is not present when lamp should light, check wiring using FO-3 to the lamp. Trace backthrough main generator circuits using FO-2 until defective wire or Item is found. Replace or replaceas required.(c) If power exists at lamp holder (23) terminals, replace lamp (21) with a known good lamp.(d) If known good lamp (21) does not light, replace lamp holder (23).(2) Replace. See Figure 5-2.(a) Remove clear lens (22) covering lamp (21). Remove lamp.(b) Tag and disconnect wires from lamp holder (23).(c) Remove lamp holder (23) from panel by removing attaching hardware.(d) Install lamp holder (23) in RCM panel. Secure with attaching hardware. Connect wiring to lampholder (23), remove and discard tags.(e) Install lamp (21).(f) Install clear lens (22).q. MASTER Switch S9R (24. Figure 5-2). MASTER switch S9R allows the operator to start or stop the generatorset from the remote control module. The toggle switch is spring loaded to return to the RUN position after having beenheld In either the START or STOP position.(1) Test.(a) Shut down the generator set. See Figure 2-23.(b) Open the RCM panel by unlocking three oval studs across the top of the panel.(c) Disconnect negative leads from MASTER switch S9R (24) terminals 3 and 4.NOTEDo not remove jumper across terminals 2 and 6.(d) Set a multimeter to RX1 scale with MASTER switch S9R in RUN position, test for continuity acrossterminals 1 and 2 and 5 and 6. Multimeter should indicate 0 ohms.(e) Hold MASTER switch S9 in START position. Multimeter should indicate zero ohms across terminals2 and 3 and 5 and 6.(f) Hold MASTER switch S9 In the STOP position Multimeter should indicate 0 ohms across terminals 1and 2 and 4 and 5.(g) Connect negative leads to terminals 3 and 4.(h) Replace MASTER switch S9R (24) if It falls any test described above.5-24
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business