ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
(2)
Remove
(a)
Set control room circuit breaker CB109 (5, Figure 2-8), located In distribution panel DP1 to OFF.
(b)
Disconnect wiring to the fan and motor assembly B103 (4, Figure 4-11) at conduit box on the fan motor
housing.
(c)
Remove hexagon head cap screws (5), lock washers (6), and flat washers (20), and remove the fan and motor
support (8) with the fan and motor assembly B103 (4).
(d)
Separate the fan and motor assembly B103 (4) from the fan and motor support (8) by removing the hexagon
head cap screws (1), lock washers (2), and self-locking nuts (3).
(3)
Install.
(a)
Secure the fan and motor assembly B103 (4, Figure 4-11 ) to the fan and motor support (8) with hexagon
head cap screws (1), lock washers (2), and self-locking nuts (3).
(b)
Install the fan and motor support (8) with the fan and motor assembly B103 (4), using hexagon head cap
screws (5), lock washers (6), and flat washers (20).
(c)
Reconnect wiring to the fan and motor assembly B103 (4) at the conduit box on the fan motor housing.
(d)
Set control room circuit breaker CB109 (5, Figure 2-8), located in distribution panel DP1, to ON.
b.
Fan Shutter Assembly.
(1)
Remove
(a)
Remove fan and motor assembly B103 (4, Figure 4-11) and fan and motor support (8) In accordance with step
a(2), above.
(b)
Remove hexagon head cap screws (5), lock washers (6), flat washers (20), and hexagonal nuts (11), and
remove the fan shutter assembly (7).
(2)
Install.
(a)
Install the fan shutter assembly (7, Figure 4-11) with hexagon head cap screws (5), lock washers (6), flat
washers (20), and hexagonal nuts (11).
(b)
Install the fan and motor assembly B103 (4) and fan and motor support (8) in accordance with step a(3),
above.
c.
Fire Extinguisher Brackets (Figure 4-11). The generator set contains three bracket mounted fire extinguishers,
one of which is located to the left and lust Inside the door to the generator set control room. The remaining two
fire extinguishers are located in the engine compartment of the generator set, one on each of the forward facing
sides of the air cleaner assemblies
NOTE
This task requires two people.
(1)
Remove. Remove the fire extinguisher bracket (14, Figure 4-11) in the generator set control room by removing
the fire extinguisher (9) from the bracket, and then removing hexagon head cap screws (10), spacers (13), lock
washers (12), and hexagonal nuts (11).
(2)
Install. Install the fire extinguisher brackets in the generator set control room (14, Figure 4-11) by installing
spacers (13), hexagon head cap screws (10), lock washers (12), and hexagonal nuts (11), and then installing the
fire extinguisher (9).
d.
Desk Top.
NOTE
This task requires two people.
(1)
Remove. Remove the desk top (15, Figure 4-11) by removing hexagon head cap screws (5) and lock washers
(6).
4-35