ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-121Set FREQ ADJ to mid-range.2Open upper cabinet B door.3See Figure 2-6 Adjust 50 CYC (8) or 60 CYC (7), as applicable on load sharing panel for FREQUENCY meter(Figure 2-14) reading of 58 to 62 Hz (for 60 Hz operation) or 48 to 52 Hz (for 50 Hz operation), as applicable4See Figure 2-6 If unable to obtain required FREQUENCY meter reading, adjust 50 CYC (8) or 60 CYC (7), asapplicable, to mid-range, adjust FREQUENCY ADJUST (3) on load sharing panel, for FREQUENCY meter(Figure 2-14) reading anywhere on scale between pegs, then repeat step 3, above.5After meeting requirements of step 3, above, close upper cabinet B door and adjust FREQ ADJ rheostat (Figure2-14) in accordance with Figure 2-14(b) If VOLT ADJ rheostat (Figure 2-14) cannot be adjusted for AC KILOVOLTS reading of 4 16 kilovolts (for 60 Hz operation) or 3.8 kilovolts (for 50 Hz operation) proceed as follows:1Set VOLT ADJ rheostat (Figure 2-14) to mid-range2Open upper cabinet B door.3Open voltage regulator cover.4See Figure 2-10. Adjust RANGE ADJ (2) for an AC KILOVOLTS (Figure 2-14) reading of 4.16 kilovoltsor 3 8 kilovolts, as applicable5If unable to obtain required AC KILOVOLTS (Figure 2-14) reading because of voltage fluctuation (hunting), check that stability selection links (1, Figure 2-10) are both set to SLOW and that STABILITY ADJ (3) Is set 1/8 turn back from full clockwise position Then repeat step 4, above6Close voltage regulator cover7Close upper cabinet B door.(11)Perform the following sub-steps If generator set will be used In droop type parallel with other generator set(s).Otherwise, proceed to step (12), below.NOTEPower factor of load must be 0 8 power factor or this procedure Is Invalid. A dc voltmeter will be required(a)Set PARALLEL SWITCH S6 (18, Figure 2-2) to PARALLEL(b)Set FREQ DROOP/ISOCHRONOUS switch S117 (12) to FREQUENCY DROOP Install shorting plug inREACTIVE LOAD receptacle J21, J22, or J23 (see Figure 2-18).(c)Set BREAKER CONTROL switch S4 (20, Figure 2-2) to CLOSE(d)Check reading on POWER FACTOR meter M104 (9). Verify load has 0 8 power factor to 48 6 for 50 Hzoperation If not, proceed as follows1Open upper cabinet B door2Refer to Figure 2-6 Adjust DROOP (4) on load sharing panel for a FREQUENCY meter (3, Figure 2-2)reading of 58 1 to 58 3 Hz for 60 Hz operation or 48.4 to 48.6 Hz for 50 Hz operation3Close upper cabinet B door.(f)Set FREQ DROOP/ISOCHRONOUS switch S117 (12) to ISOCHRONOUS(g)Remove shorting plug from REACTIVE LOAD receptacle J21, J22, or J23 (Figure 2-18).4-17
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business