ARMY TM 9-6115-464-34AIR FORCE TO 35C2-3-445-2NAVY NAVFAC P-8-624-34Table 2-2. TROUBLESHOOTING (CONTINUED)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONStep 3. Defective ac ammeter.Replace ac ammeter (para. 3-59).Step 4. Defective current transformer CT1, CT2, OR CT3 (10, figure 3-108).Test and replace defective transformers (para. 3-86).23. WATT METER FAILS TO REGISTER.Step 1. Defective control cubicle wiring harness assembly (figure 3-59).Repair or replace control cubicle wiring harness assembly (para. 3-59).Step 2. Defective thermal watt converter or watt meter.Replace thermal watt converter and watt meter (para. 3-59).24. FREQUENCY DRlFTS.Step 1. Governor control unit out of alignment (Precise sets only).Align governor control unit (para. 3-64, electro–hydraulic governor or 3-85, electricgovernor equipped precise sets).Step 2. Engine runs erratically.See Malfunction 4 of this table.2-13