Section V. APPLICATIONS KIT
Figure 5-23. Plate and Sleeve Assembly Removal - TM-9-6115-464-34_457
TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
429
430
431
432
433
434
435
436
437
438
439
ARMY TM 9-6115-464-34
AIR FORCE TO 35C2-3-445--2
NAVY NAVFAC P-8-624-34
Table 5-3. APPLICATIONS KIT TROUBLESHOOTING CHART
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. REMOTE LOW FUEL MONITOR NOT FUNCTIONING
Step 1. Defective printed circuit band (PCB) inside remote housing (11, figure 5-29).
Replace remote functions assembly (para 5-27).
Step 2. Defective cable assembly (figure 5-27).
Repair cable assembly (para 5-26)
Step 3. Defective K3 relay on remote housing (figure 5-31).
Replace remote functions assembly (para 5-27).
Step 4. Defective relay wire harness or relay socket (figure 5-29).
Replace remote functions assembly (para 5-27).
2.
GENERATOR
SET DOES NOT RESPOND TO REMOTE STOP SIGNAL
Step 1. Defective cable assembly (figure 5-27).
Repair cable assembly (para 5-26).
Step 2. Defective
relay
K2 on remote housing (figure 5-31).
Replace remote functions assembly (para 5-27).
Step 3. Defective relay socket harness or relay socket (figure 5-29).
Replace remote functions assembly (para 5-27).
3.
GENERATOR
SET DOES NOT RESPOND TO REMOTE BATTLE SHORT SIGNAL
Step 1. Defective cable assembly (figure 5-27).
Repair cable assembly (para 5-26).
Step 2. Defective
relay
K1 on remote housing (figure 5-31).
Replace remote functions assembly (para 5-27).
Step 3. Defective relay wire harness or relay socket (figure 5-29).
Replace remote functions assembly (para 5-27).