ARMY TM 9-6115-464-34AIR FORCE 35C2-3-445-2NAVY NAVFAC P-8-624-34NOTES:1.2.3.4.ALL SOLDERED CONNECTIONS SHALL BE5.IN ACCORDANCE WITH MIL-STD-454,6.REQUIREMENT 5.CUT INSULATION SLEEVING, FIND NO. 7,7.INTO 24 PIECES, .750 INCHES LONG ANDINSTALL OVER WIRES AND PINS, AFTER8.SOLDERING, TO THE CONNECTORS, FINDNOS. 3,2, AND 1. THEN APPLY HEAT OF400° F FOR 3-5 SEC. FOR PROPER9.SHRINKAGE.INSTALL STRAPS, FIND NO. 9, ATAPPROXIMATELY 2.5 INTERVALS AND ATEACH WIRE BREAKOUT.WIRE MARKING TO BE IN ACCORDANCEWITH MIL-W-5088 EXCEPT THAT LENGTHBETWEEN GROUPS OF NUMBERS SHALLNOT EXCEED 6 INCHES.INTERPRET DRAWING PER MIL-STD-100.CRIMPED TERMINAL SHALL MEET THEPERFORMANCE REQUIREMENTS OF MIL-T-7928.INSTALL END SEAL PLUGS, FIND NO. 8, IN UNUSED HOLESOF CONNECTORS, FIND NOS. 1,2, AND 3.REF: CONNECTION DIAGRAM 72-2631SCHEMATIC DIAGRAM 72-2630AND 72-2629ALL WIRES WITHOUT TERMINAL LUGSSHALL BE STRIPPED .25 FROM THE ENDAND TINNED IN ACCORDANCE WITHMIL-STD-454, REQUIREMENT 5.A. Static Exciter Wiring Harness (Sheet 1 of 2)Figure 3-133. Static Exciter Wiring Harness, Dwg. No. 72–2628, Voltage Regulator Wiring Harness,Dwg. No. 72–2627, and Static Exciter Connection Wiring Diagram, Dwg. No. 2-2631 (Sheet 1 of 4)3-280