ARMY TM 9-6115-464-12
AIR FORCE TO 35C2-3-445-1
NAVY NAVFAC P-8-624-12
(d) Load bank kit:
DOD drawing number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-2803
Load rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 KW
Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120/208 or 240/416 Vac 3 Phase 4 wire
(e) Applications kit:
MERADCOM drawing number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13220E8189
Load rating . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 840 watts
Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Vdc
(f)
Acoustic
suppression kit:
Model number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MEP-004AAS
Weight increase to generator set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1292 lb.
Cube of generator set with kit installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178.2 cubic feet
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
Fuel System
Diagram. Refer to Figure 1-7.
Hydraulic System Diagram. Refer to Figure 1-12.
AC and DC, 15 and 30KW, 50/60 and 400 Hz, Precise and Utility, Wiring Diagram, Dwg. No.
72-2205. Refer to figure FO-1.
AC
Schematic Diagram
, 15 and 30 KW, Precise Generator Sets, Dwg. No. 72-2200. Refer to figure FO-2.
DC
Schematic Diagram
, 15 and 30 KW, Precise Generator Sets, Dwg. No. 72-2269. Refer to figure FO-3.
AC Schematic Diagram, 15 and 30KW, Utility
Generator
Sets, Dwg. No. 72-2295. Refer to figure FO-4.
DC Schematic Diagram, 15 and 30KW, Utility
Generator
Sets, Dwg. No. 72-2277. Refer to figure FO-5.
Shipping Dimensions and Weights. Refer to Figure 1-3.
1-12 DIFFERENCES BETWEEN MODELS.
The primary differences between the models of the generator sets
covered in this manual are as follows:
a.
b.
c.
d.
e.
f.
1-12
Models MEP-004A and MEP-103A are equipped with a 50/60 Hz generator. Model MEP-113A is
equipped with a 400 Hz generator.
Models MEP-103A and some MEP-113A use an electro-hydraulic governor. Other Models MEP-113A
use an electric govemor. Model MEP-004A uses a mechanical governr which is integral with the fuel
injection pump.
The control cubicle of all three models have a
frequency
adjust rheostat, but it is functional only on models
MEP-103A and MEP-113A. Model MEP-004A accomplishes
frequency
adjustment through the manual
speed control.
All three models use the same special
relay
box, but models MEP-103A and MEP-113A are also equipped
with a precise relay box. The two precise relay boxes are identical with the exception that the precise relay
box of model MEP-103A contains a frequency selector switch whereas the precise
relay
box of model
MEP-113A does not.
Models MEP-103A and MEP-004A use the same
exciter
regulator assembly and crosscurrent transform-
er. These components are different on model MEP-113A.
Differences in performance characteristics are given in Table 1-1.