TM5-6115-634-14&PNAVFAC P-8-647-14&PT0-35C2-3-445-14TM-6115-14&P/1Table 4-2.PU 794/6, TROUBLESHOOTING PROCEDURES (CONT)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION2.APPROPRIATE INDICATOR LAMP DOES NOT ILLUMINATE AT REMOTE CONTROL UNIT.Step 1.Check indicator lamp for open filament.Replace lamp if filament is open.Step 2.Refer to FO-2 and test control cables and junction box forcontinuity in indicator lamp circuit.Replace faulty cable or junction box.Step 3.Test remote control unit.Replace faulty remote control unit.Step 4.If indicator lamp still does not illuminate, remote functionsbox assembly is faulty.Report to intermediate direct supportSection IV.MAINTENANCE PROCEDURESmaintenance.4-9. General InstructionsPU 794/G.Each maintenance functionwill be performed with the PU 794/G shutThis section provides organizationaldown and negative battery cable discon-maintenance instructions for thenected, except where otherwise stated.4-7