TM5-6115-634-14&P
NAVFAC P-8-647-14&P
T0-35C2-3-445-14
TM-6115-14&P/1
Table 4-2.
PU 794/6, TROUBLESHOOTING PROCEDURES (CONT)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2.
APPROPRIATE INDICATOR LAMP DOES NOT ILLUMINATE AT REMOTE CONTROL UNIT.
Step 1.
Check indicator lamp for open filament.
Replace lamp if filament is open.
Step 2.
Refer to FO-2 and test control cables and junction box for
continuity in indicator lamp circuit.
Replace faulty cable or junction box.
Step 3.
Test remote control unit.
Replace faulty remote control unit.
Step 4.
If indicator lamp still does not illuminate, remote functions
box assembly is faulty.
Report to intermediate direct support
Section IV.
MAINTENANCE PROCEDURES
maintenance.
4-9. General Instructions
PU 794/G.
Each maintenance function
will be performed with the PU 794/G shut
This section provides organizational
down and negative battery cable discon-
maintenance instructions for the
nected, except where otherwise stated.
4-7