TM 5-6115-593-12
TO 35C2-3-463-1
Table 5-1. OPERATOR/CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICES, REMOTE CONTROL
MODULE.
NOTE: Within designated interval, these checks are to be performed in the order listed.
B-Before
A-After
D-During
Item
INTERVAL
ITEMS TO BE
PROCEDURES
CHECK FOR AND HAVE REPAIRED
EQUIPMENT IS
NOT READY/
No.
B
D
A
INSPECTED
OR ADJUSTED AS NECESSARY
AVAILABLE IF:
1
o
Remote
Control
Module
Inspect controls, gauges, lamps and
instruments daily for damage, loose
mounting or loose connections.
5-6.
OPERATOR/CREW TROUBLESHOOTING.
Table 5-2 contains troubleshooting information for use in
correcting operating troubles which may develop in the
generator set when used with the remote control
module. Each malfunction is followed by a list of tests
or inspections which will help to determine probable
causes and corrective actions to take. Perform the tests
or inspections and corrective actions in the order listed.
Any
trouble
beyond
the
scope
of
crew
level
maintenance should be referred to the next higher
(organizational) level of maintenance.
NOTE
Before referring to table 5-2, be sure that all
applicable checks have been performed.
5-7.OPERATOR/CREW
MAINTENANCE
OF
THE
REMOTE CONTROL MODULE. This paragraph
includes instructions to assist the operator/crew in
maintaining the remote control module. If, during
inspections, defective components are noted, refer to
next higher level of maintenance for replacement or
repair.
a.
Inspection. Inspect components on the front
panel, inside the enclosure, and on the mounting plate
as follows:
(1) Inspect
all
gauges,
switches,
and
instruments on front panel for cracking or
damage,
loose
mounting
or
loose
connections.
(2) Inspect the telephone jack (30, figure 2-14)
for damage, loose mounting, or loose
connections.
(3) Inspect the panel lamps (19, figure 2-14) for
loose mounting or loose connections.
(4) Inspect transformer (29, figure 5-2) for
cracking or damage, loose mounting or
loose connections.
b. Replacement.
(1) Replace
defective
bulbs
in
lamp
assemblies.
(2) Replace defective telephone jack as follows:
(a) Tag and remove wires connected to the
jack.
(b) Remove the hex nut and flatwasher
attaching jack to panel, and remove jack.
(c) Install jack and secure with flatwasher
and hex nut.
(d) Connect wires and remove wire tags.
5-8.
ORGANIZATIONAL TROUBLESHOOTING.
Table 5-3 provides information for locating and
correcting operating troubles which may develop in the
generator set when used with the remote control
module. Each malfunction is followed by a list of tests
or inspections which will help to determine probable
causes and corrective actions to take. Perform the tests
or inspections and corrective actions in the order listed.
Any trouble beyond the scope of